(1)Real time reading of parameters such as voltage, temperature, and total current from the battery detection module, and uploading them to the remote monitoring platform;
(3) The address of the battery monitoring module has an automatic allocation function, making installation and debugging easy;
(4) High safety, with multiple protections such as power isolation, optocoupler isolation, and fuse protection, does not affect the operation of the battery pack;
(5) Modular structure design allows for flexible configuration of different quantities of battery packs, achieving low-cost solutionsplan;
(6) The circuit port has EMC design and strong anti electromagnetic interference capability, especially for high-frequency UPS battery packs, which can achieve high measurement accuracy.
Name | Parameters | Remarks | |
work condition | input power | 12VDC | 10~15VDC |
power consumption | <3W | ||
ambient temperature | -10℃~50℃ | ||
ambient humidity | 10%~90%RH, non-condensing | ||
report Communication port | address range | 1-254255 is the broadcast address | Default Address 1 |
interface method | RS485 | Photoelectric isolation | |
communication parameters | 9600、 N、8、1 | ||
battery collect interface | Number of batteries | 48section | RJ11interface |
interface method | current loop | Photoelectric isolation | |
communication parameters | 9600、 N、8、1 | ||
current sensor | Number of collection channels | 1road | Test 1 set of batteries |
input signal | 4~20mA | ||
Collection accuracy | 1% FS | Related to sensor accuracy | |
alternate route | Number of collection channels | 2road | |
input signal | 0-2.5V | ||
Collection accuracy | 1% FS | Related to sensor accuracy | |
housing material | Flame retardant ABS plastic, grade 94V-0 | ||
housing dimensions | L*W*H: 62*56*26mm | ||